19 mch pid setpoint control, 1 feedback devices – Lenze MCH Series User Manual

Page 75

Advertising
background image

13435744_EDBMH01_v13

71

19

MCH PID SETPOINT CONTROL

PID Setpoint Control allows the MCH drive to maintain a process setpoint, such as PSI

or CFM, without using an external controller. When PID is activated (and the drive is in

AUTO mode), the MCH will operate in a closed-loop fashion, automatically adjusting the

motor speed to maintain the setpoint.
PID setpoint control requires feedback from the process in order to compare the process

variable “value” to the setpoint. The difference between the process variable “value” and

the setpoint is called the error. The MCH will increase or decrease the motor speed

in an attempt to minimize the error. By constantly adjusting the motor speed, the PID

control will drive the process toward the setpoint. Refer to the PID block diagram below.

SETPOINT

Process Variable

Feedback (transducer)

Motor

Error

Speed

Command

P

I

D

Process

19.1

FEEDBACK DEVICES

A transducer or transmitter is required to monitor the process variable and provide

feedback to the PID unit in order to compare the process variable feedback to the

setpoint. A transducer outputs a signal corresponding to a fixed range of the process

variable. A transmitter provides offset and gain adjustments to allow the output signal

to be adjusted to correspond to different ranges of the process variable. Typical output

signals for transducers and transmitters are: 0-5 VDC, 0-10 VDC, or 4-20 mA. The

feedback device must be externally powered, as the drive does not have a power supply

for such devices. Program Parameter 74 - PID FEEDBACK for the appropriate terminal

(TB-5A or TB-5B), and connect the feedback device as described below:
POT

The positive signal wire (wiper) is connected to TB-5A, and the “high”

lead is connected to TB-6.

0-5, 0-10 VDC

Connect the positive signal wire to TB-5A.

4-20 mA

Connect the positive signal wire to TB-5B.

The common, or negative signal wire, is connected to TB-2 (circuit common).
Feedback devices can be direct or reverse acting. A direct acting device outputs a

signal that increases as the process variable increases. A reverse acting device

outputs a signal that decreases as the process variable increases. The programming of

Parameters 75 - FEEDBACK @ MIN and 76 - FEEDBACK @ MAX depend on the type

of feedback device being used.
When using a direct acting transducer, Parameter 75 - FEEDBACK @ MIN should

be set to the value of the process variable feedback corresponding to the minimum

feedback signal (0 VDC or 4 mA), and Parameter 76 - FEEDBACK @ MAX should

be set to the value of the process variable feedback corresponding to the maximum

feedback signal (5 or 10 VDC, or 20 mA). Refer to the example herein.

Advertising