Lenze MCH Series User Manual

Page 59

Advertising
background image

13435744_EDBMH01_v13

55

24

AUTO SOURCE

This parameter selects the speed reference source that the drive will follow when it is in

AUTO mode. The following options are possible:
KEYPAD The

p

and q keys control the drive speed.

0-10 VDC

The drive will follow a 0-10 VDC signal wired between TB-5A (+)

and TB-2 (-).

4-20 MA

The drive will follow a 4-20 mA signal wired between TB-5B (+) and

TB-2 (-).

PRESET #1 - #4

The drive will run at a programmable preset speed. Refer to

Parameters 1-4.

MOP

The drive speed is controlled by two contacts (one to increase the

speed and the other to decrease the speed). Program TB-13A

(Parameter 47) to DECREASE FREQ, and TB-13B (Parameter 48)

to INCREASE FREQ. Closing TB-13A to TB-2 will decrease the

speed, and closing TB-13B to TB-2 will increase the speed. Refer

to Section 14.2.4.

SELECTED

The drive speed will be determined by whatever speed reference

is selected using the TB-13 terminals. Refer to Parameters 47, 48,

and 49.

25

START METHOD

WARNING!

Automatic start of equipment may result in damage to equipment

and/or injury to personnel! Automatic start should only be used on

equipment that is inaccessible to personnel

This parameter selects the starting method for the drive, and can be set for one of the

following:
NORMAL

The drive will start when the appropriate contact closure is made

on the terminal strip (in REMOTE mode), or by pressing the keypad

START key (in LOCAL mode). To start the drive in NORMAL mode,

a start command must be issued at least two seconds AFTER input

power is applied.

POWER UP

The drive will automatically start upon application of input power.

The drive MUST be in AUTO mode, and the start command MUST

be present when power is applied for this function to operate.

AUTO 1

FLYING AUTO RESTART - LOW performance. Synchronization in

approximately 6 seconds with current levels up to 50% of the drive

rating. This setting results in a slow, smooth synchronization.

AUTO 2

FLYING AUTO RESTART - MEDIUM performance. Synchronization

in approximately 1 second with current levels up to 50% of the drive

rating. This setting allows faster synchronization while retaining

smoothness.

AUTO

3

FLYING AUTO RESTART - HIGH performance. Synchronization

in approximately 1 second with current levels up to 100% of the

drive rating. This setting allows the fastest synchronization, but

sacrifices smoothness.

Advertising