13435744_EDBMH01_v13

39

15.4

SPEED POT AND PRESET SPEED CONTROL

In this example, the drive is in Keypad H/O/A mode. In HAND mode, speed is controlled

from the speed pot. In AUTO mode, speed is controlled by the selected PRESET

SPEED.

RUN / ST

OP

CIR
CUIT C

OMMON

0-10 VDC

INPUT

1 2 5A 5B 6 10A

12A

RXA TXB

10B 2

13A 13B 13C 13D 14 15 2

16 17 18

FORM C

RELAY

CIR
CUIT C

OMMON

MAINTAINED

RUN/STOP

CONTACT

The TB-2 terminals are internally tied together

PRESE

T SPEED #1

PRESE

T SPEED #3

CIR
CUIT C

OMMON

PRESE

T SPEED #2

SPEED POT

(10 K)

10 VDC

SUPPL

Y

NOTES:
1.

Program the PRESETS (Parameters 1-4) to the desired values.

2.

Program TB-13A to PRESET #1, TB-13B to PRESET #2, and TB-13C to PRESET

#3 (Parameters 47-49). Close any two to select PRESET #4.

3.

Program HAND SOURCE (Parameter 29) to 0-10 VDC. In HAND mode, the speed

will be controlled by the speed pot.

4.

Program AUTO SOURCE (Parameter 24) to SELECTED. In AUTO mode, the

speed will be controlled by the preset speeds.