2 the system - direct and reverse acting, 3 pid control - direct and reverse acting – Lenze MCH Series User Manual

Page 76

Advertising
background image

72

13435744_EDBMH01_v13

Example 1: A 0-100 psi transducer outputs a 4 mA signal at 0 psi and 20 mA at 100

psi. Program Parameter 75 to 0.0 PSI and Parameter 76 to 100.0 PSI (this

assumes that Parameter 31 - UNITS is set to pid: PSI and Parameter 33 -

UNITS DECIMAL is set to XXX.X).

For a reverse acting transducer, set Parameter 75 - FEEDBACK @ MIN to the maximum

process variable feedback value, and set Parameter 76 - FEEDBACK @ MAX to the

minimum process variable feedback value. In other words, Parameter 75 is set higher

than Parameter 76. Refer to Example 2.
Example 2: A 0-100 psi transducer outputs a 20 mA signal at 0 psi and 4 mA at 100

psi. Program Parameter 75 to 100.0 PSI and Parameter 76 to 0.0 PSI

(This assumes that Parameter 31 - UNITS is set to pid: PSI, and Parameter

33 - UNITS DECIMAL is set to XXX.X).

19.2

THE SYSTEM - DIRECT AND REVERSE ACTING

The entire system can also be direct or reverse acting. In a direct acting system, an

increase in motor speed causes an increase in the process variable. This is equivalent

to requiring an increase in motor speed in response to a decreasing process variable

feedback.
In a reverse acting system, an increase in motor speed causes a decrease in the

process variable. This is equivalent to requiring an increase in motor speed in response

to an increasing process variable feedback. Examples of direct and reverse acting

systems are described in the next section.

19.3

PID CONTROL - DIRECT AND REVERSE ACTING

The PID Setpoint Control software can be direct or reverse acting, and must be set to

match the system. This is accomplished with Parameter 70 - PID MODE. When set to

NORMAL (for direct acting systems), the PID unit will command an increase in motor

speed if the process variable feedback decreases, and a decrease in motor speed if

the process variable feedback increases. When set to REVERSE (for reverse acting

systems), the opposite is true.
NOTE:

Do not use the REVERSE setting for Parameter 70 - PID MODE to

compensate for reverse acting feedback devices. If a reverse acting

feedback device is used, program Parameters 75 and 76 as described

above in Section 19.1.

An example of a direct acting system is one that maintains duct pressure. Duct pressure

is the process variable that is monitored by the feedback device. As duct pressure

rises, motor speed needs to be decreased to maintain the pressure. A direct acting PID

control will command a decrease in motor speed in response to an increasing process

variable feedback.
An example of a reverse acting system is one that maintains water temperature in

a cooling tower. Water temperature is the process variable that is monitored by the

feedback device. As the water temperature rises, motor speed needs to be increased

to lower the temperature of the water. A reverse acting PID control will command an

increase in motor speed in response to an increasing process variable feedback.

Advertising