13435744_EDBMH01_v13

35

Once the desired speed is reached, release the contact and the drive speed will hold

at that value. The DECREASE FREQ function will work when the drive is in a STOP

or RUN mode. The INCREASE FREQ function will only work while the drive is in a

RUN mode.
If HAND SOURCE and/or AUTO SOURCE is set to SELECTED, TB-13A and TB-13B

can be programmed for this function. Program TB-13A (Parameter 47) to DECREASE

FREQ, and TB-13B (Parameter 48) to INCREASE FREQ. Refer to the description of

operation in the preceding paragraph.

NOTE

If TB-13A, TB-13B and TB-13C are all programmed to select speed

references, and two or three of the terminals are closed to TB-2,

the higher terminal has priority and will override the others. For

example, if TB-13A is programmed to select 0-10VDC, and TB-13C

is programmed to select PRESET #3, closing both terminals to TB-2

will cause the drive to respond to PRESET #3 because TB-13C

overrides TB-13A.

14.2.5

ANALOG OUTPUT SIGNALS

There are two terminals that can supply analog output signals proportional to output

frequency and load. Terminal TB-10A can provide a 0-10 VDC or a 2-10 VDC signal

proportional to output frequency, and TB-10B can provide the same signals proportional

to load. The 2-10 VDC signals can be converted to a 4-20 mA signal using a resistor

in series with the signal such that the total circuit resistance is 500 Ohms. For more

information, refer to Parameters: 42 - TB10A OUTPUT, 43 - TB10A SCALING, 44 -

B10B OUTPUT and 45 - TB10B SCALING in Section 18.0 - DESCRIPTION OF

PARAMETERS.

14.2.6

DRIVE STATUS OUTPUTS

The control board has one Form C relay at terminals TB-16, TB-17 and TB-18. Contacts

are rated 2 amps at 28 VDC or 120 Vac.
There are also two open-collector outputs at terminals TB-14 and TB-15. The open-

collector circuit is a current-sinking type rated at 30 VDC and 40 mA maximum. A power

supply (30 VDC max) must be used to power the open-collector outputs. The standard

drive does not have a power supply (a 24 VDC power supply is optional when the drive

is equipped with the Bypass option).
The Form C relay and open-collector outputs can be programmed for many different

status indications. Refer to Parameters 52 - TB14/RELAY #2, 53 - TB15/RELAY #3,

and 54 - RELAY #1.

NOTE

The Bypass option includes two Form C relays and a third is optional

(refer to Appendix A). When the drive is equipped with the Option

Box, there are two Form C relays and two open-collector outputs

(refer to Appendix B).