11 mch power wiring diagram – Lenze MCH Series User Manual

Page 28

Advertising
background image

24

13435744_EDBMH01_v13

11

MCH POWER WIRING DIAGRAM

This diagram applies to standard MCH drives. Refer to Appendix A for Bypass power

wiring or Appendix B for Option Box power wiring.

T1 T2 T3

L1 L2 L3

FUSED INPUT

VOLTAGE

GND

GND

GND

DISCONNECT

MEANS

(REQUIRED)

THREE PHASE

AC MOTOR

WARNING!

Do NOT connect incoming AC power to output terminals T1, T2 or

T3. Severe damage to the drive will result.

INSTALL, WIRE AND GROUND IN ACCORDANCE WITH ALL APPLICABLE CODES.
NOTES:
1.

Wire the motor for the proper voltage per the output rating of the drive. Motor wires

MUST be run in a separate steel conduit away from control wiring and incoming

AC power wiring.

2.

Do not install contactors between the drive and the motor without consulting Lenze

AC Tech for more information. Failure to do so may result in drive damage.

3.

Remove any existing, and do not install, power factor correction capacitors

between the drive and the motor. Failure to do so will result in drive damage.

4.

Use only UL and CSA listed and approved wire.

5.

Minimum wire voltage ratings: 300 V for 200 and 240 Vac systems and 600 V for

400, 480, and 590 Vac systems.

6.

Wire gauge must be based on a minimum of 125% of the rated output current of

the drive, and a minimum 75°C insulation rating. Use copper wire only.

7.

Wire and ground in accordance with NEC or CEC, and all applicable local codes.