3 remote h/o/a – Lenze MCH Series User Manual

Page 42

Advertising
background image

38

13435744_EDBMH01_v13

15.3

REMOTE H/O/A

Shown below is the wiring diagram for selecting H/O/A from the terminal strip. Also

shown is the wiring for a 0-10 VDC or 4-20 mA speed reference signal. In HAND mode,

TB-1 must be closed to TB-2 in order to start the drive. In AUTO mode, close TB-1 to

TB-2 to RUN, and open to STOP.

RUN / ST

OP

CIR
CUIT C

OMMON

0-10 VDC

INPUT

4-20 mA INPUT

1 2 5A 5B 6 10A

12A

RXA TXB

10B 2

13A 13B 13C 13D 14 15 2

16 17 18

FORM C

RELAY

CIR
CUIT C

OMMON

MAINTAINED

RUN/STOP CONTACT

(AUTO MODE ONLY)

The TB-2 terminals are internally tied together

AUT

O MODE SELEC

T

HAND MODE SELEC

T

CIR
CUIT C

OMMON

HAND

OFF

AUTO

HAND

OFF

AUTO

NOTES:
1.

Program TB-13C (Parameter 49) to HAND. This forces TB-12A to act as AUTO.

2.

In AUTO mode (TB-12A closed to TB-2), close TB-1 to TB-2 to RUN, and open to

STOP. The speed reference will be determined by AUTO SOURCE (Parameter

24).

3.

When HAND mode is selected (TB-13C closed to TB-2), TB-1 must also be

closed to TB-2 in order to RUN. The speed reference will be determined by HAND

SOURCE (Parameter 29).