17 parameter menu, Parameter menu – Lenze MCH Series User Manual

Page 46

Advertising
background image

42

13435744_EDBMH01_v13

17

PARAMETER MENU

Contained in this section is a list of the MCH Series parameters in ascending numnerical

order. Refer to Section 18 DESCRIPTION OF PARAMETERS for full information on

each parameter.

PARAMETER MENU

PARAMETER

NUMBER

PARAMETER

NAME

RANGE OF

ADJUSTMENT

FACTORY

DEFAULT

0

LINE VOLTS

HIGH

LOW

AUTO

AUTO

1

PRESET #1

(NOTE 1)

20.00 Hz

2

PRESET #2

(NOTE 1)

20.00 Hz

3

PRESET #3

(NOTE 1)

20.00 Hz

4

PRESET #4

(NOTE 1)

20.00 Hz

5

SKIP FREQ #1

.00 Hz - MAXIMUM FREQ

.00 Hz

6

SKIP FREQ #2

.00 Hz - MAXIMUM FREQ

.00 Hz

7

BANDWIDTH

.00 - 10.00 Hz

1.00 Hz

8

ACCEL RATE

(NOTE 1)

30.0 SEC

9

DECEL RATE

(NOTE 1)

30.0 SEC

10

MINIMUM FREQ

.00 - MAXIMUM FREQ

.50 Hz

11

MAXIMUM FREQ

MINIMUM FREQ - 120.0 Hz

60.00 Hz

12

DC BRAKE VOLT

(NOTE 1)

.0 VDC

13

DC BRAKE TIME

.0 - 999.9 SEC

.0 SEC

14

DYNAMIC BRAKE

OFF, ON

OFF

16

CURRENT LIMIT

25 - 120 %

120 %

17

MOTOR OVRLOAD

25 - 100 %

100%

18

BASE FREQ

20.00 - 360.0 Hz

60.00 Hz

19

FIXED BOOST

.0 - 30.0 %

(NOTE 1)

22

TORQUE

CONSTANT

VARIABLE

CONST / NO COMP

CONSTANT

23

CARRIER FREQ

2.5, 6, 8, 10, 12, 14 kHz

2.5 kHz

24

AUTO SOURCE

KEYPAD

0-10 VDC

4-20 MA

PRESET #1

PRESET #2

PRESET #3

PRESET #4

MOP

SELECTED

4-20 MA

NOTE 1: REFER TO SECTION 18.0 - DESCRIPTION OF PARAMETERS.

Advertising