3 technical data, 1 general data/ application conditions, 1 general data/application conditions – Lenze 8200 series User Manual

Page 13: Technical data

Advertising
background image

Technical Data

UOMu_^MVMO

3-1

3 Technical data

3.1 General data/application conditions

Field

Values

Vibration resistance Germanischer Lloyd, general conditions
Humidity class

Humidity class F without condensation (average relative humidity 85 %)

Permissible

t

t

during transport of the controller: -25

°C ¼ +70 °C

Permissible

temperature ranges during storage of the controller: -25 °C ¼ +55 °C

during operation of the controller:

0

°C ¼+40 °C

+40

°C ¼ +50 °C

without power derating
with power derating

Permissible

installation height h

h ≤ 1000 m.a.m.s.l

1000 m a.m.s.l < h ≤ 4000 m a.m.s.l

without power derating
with power derating

Degree of pollution

VDE 0110 part 2 pollution degree 2

Noise emission

Requirements acc. to EN 50081-2, EN 50082-1, IEC 22G-WG4 (Cv) 21
Limit value class A to EN 55011 (industrial area) with mains filter
Limit value class B to EN 55022 (residential area) with mains filter and installation into

control cabinet

Noise immunity

Limit values maintained usig mains filter
Requirements according to EN 50082-2, IEC 22G-WG4 (Cv) 21
Requirements

Standard

Severities

ESD

EN61000-4-2

3, i.e. 8 kV with air discharge
6 kV with contact discharge

RF interference(enclosure)

EN61000-4-3

3, i.e. 10 V/m; 27

¼1000 MHz

Burst

EN61000-4-4

3/4, i.e. 2 kV/5 kHz

Surge
(Surge on mains cable)

EN 61000-4-5

3, i.e. 1.2/50 μs,
1 kV phase-phase,
2 kV phase-PE

Insulation strength

Overvoltage category III according to VDE 0110

Packaging

(DIN 4180)

Dust packaging

Type of protection

IP20
NEMA 1: Protection against contact

Approvals

CE:

Low Voltage Directive
Electromagnetic compatibility

Show/Hide Bookmarks

Advertising