Installation – Lenze 8200 series User Manual

Page 27

Advertising
background image

Installation

UOMu_^MVMO

4-11

Terminal Use

(Factory setting is printed in bold)

Level

Data

Analog
i

t

7

GND 1

inputs

8

Setpoint input,

reference:

Terminal 7
(0 to 10V)

S

Q

O

R

P

N

5 - 6
5 - 6
3 - 4
1 - 2

0 to 20 mA
4 to 20 mA
0 to 5 V
0 to 10 V

Resolution: 9 bit
Linearity fault:

±0.5 %

Temperature fault: 0.3 % (0...+40

°C)

Input resistance
Voltage signal: > 100 kΩ

Jumper

Voltage signal: > 100 kΩ

Current signal: 250 Ω

9

Supply for setpoint potentiometer

5.2V / 6mA

Analog
output

62

Analog output, reference: terminal 7
(Field frequency)

0... 6 V / 2

mA

Resolution: 8 bit

Digital

inputs

20

Voltage supply for digital inputs
12 V/20 mA

p

28

Controller enable

HIGH

HIGH: 12 V ... 30 V

E4

CW rotation/
CCW rotation (CW/CCW)

CW: LOW
CCW: HIGH

HIGH: 12 V ... 30 V
LOW: 0 V ... 3 V

E3

DC-injection brake

HIGH

E2

JOG frequencies

Binary code

E1

JOG eque c es
20Hz, 30Hz, 40Hz

a y code

39

GND 2 (reference for external voltages)

Terminal Use

(Factory setting is printed in bold)

Relay position

(switched)

Data

Relay

output

K1

K 11

Relay output normally-closed contact
(TRIP)

opened

24 V AC / 3,0 A or
60 V DC / 0.5 A

p

K1

K 12

Relay mid-position contact

60 V DC / 0.5 A

K 14

Relay output normally-open contact
(TRIP)

closed

Show/Hide Bookmarks

Advertising