Configuration – Lenze 8200 series User Manual

Page 57

Advertising
background image

Configuration

UOMu_^MVMO

7-9

Code

IMPORTANT

Possible settings

Name

Code

IMPORTANT

Info

Selection

Lenze

Name

C117

¿

Function relay

K2

822X/824X

-0-

-0- Ready for operation
-1- TRIP fault message
-2- Motor is running
-3- Motor is running / CW rotation
-4- Motor is running / CCW rotation
-5- Field frequency f

d

= 0

-6- f

dSet

reached

-7- Q

min

reached

-8- I

max

reached

-9- Overtemperature (

J

max

-10

°C)

-10- TRIP or Q

min

or IMP

-11- PTC warning

C119

¿

Function PTC

822X/824X

-0-

-0- PTC input inactive
-1- PTC input active,

TRIP and IMP (pulse inhibit) are set

-2- PTC input active, warning

C120 I

2

¡ t switch off

822X/824X

0

0

{1 %}

100

C125

¿*

LECOM baud

rate

-0-

-0- 9600 baud
-1- 4800 baud
-2- 2400 baud
-3- 1200 baud
-4- 19200 baud

Only for

LECOM

applications

C142

¿

Start condition

-1-

-0- Automatic start inhibited, flying-restart

circuit inactive

-1- Automatic start, if term. 28 HIGH,

flying-restart circuit not active

-2- Automatic start inhibited, flying-restart

circuit active

-3- Automatic start, if term. 28 HIGH,

flying-restart circuit active

Show/Hide Bookmarks