3 installation of a ce-typical drive system, Installation – Lenze 8200 series User Manual

Page 29

Advertising
background image

Installation

UOMu_^MVMO

4-13

4.3 Installation of a CE-typical drive system

General

notes

D

The user is responsible for the compliance of his application with the EC directives.
- If you observe the following measure you can be sure that the drive system will not cause any

EMC problems, i.e. comply with the EMC Directive when running the machine.

- If devices which do not comply with the CE requirement concerning noise immunity EN 50082-2

are operated close to the controller, these devices may be interfered electromagnetically by the

controllers.

Assembly D Connect controller, mains choke, and mains filter to the grounded mounting plate with a wire of

large a cross-section as possible:
- Mounting plates with conductive surfaces (zinc-coated, stainless steel) allow permanent contact.
- Varnished boards should not be used for installation in accordance with EMC

D

If you use several mounting plates:
- Connect as much surface as possible of the mounting plates (e.g. with copper bands).

D

Ensure the separation of motor cable and signal or mains cable.

D

Do not use the same terminal strip for mains input and motor output.

D

Cable guides as close as possible to the reference potential. Unguided cables have the same effect

as aerials.

Filters

D

Use mains filters or RFI filters and mains chokes which are assigned to the controller:
- RFI filters reduce impermissible high-frequency interference to a permissible value.
- Mains chokes reduce low-frequency interferences which depend on the motor cable and its

length.

- Mains filters combine the functions of mains choke and RFI filter.