3 maloperation of the drive, 2 fault analysis using the history buffer, Troubleshooting and fault elimination – Lenze 8200 series User Manual

Page 60

Advertising
background image

Troubleshooting and fault elimination

8-2

UOMu_^MVMO

8.1.3

Maloperation of the drive

Maloperation

Possible causes

Motor does not rotate

D

DC-bus voltage too low

(red LED is blinking every 0.4 s; message LU is displayed)

D

Controller inhibited

(green LED is blinking, display of the operating module: OFF,

STOP or AS_LC)

D

Setpoint = 0

D

DC braking active

D

Quick-stop function active

D

JOG setpoint activated and JOG frequency = 0

D

Fault is indicated (see chapter 8.3 )

D

Mechanical motor brake is not released

Motor does not rotate

smoothly

D

Defective motor cable

D

Maximum current C022 and C023 too low

D

Motor underexcited or overexcited (check parameter setting)

Current consumption of

motor too high

D

Setting of C016 too high

D

Setting of C015 too low

D

C088 and C091 are not adapted to the motor data.

8.2 Fault analysis using the history buffer

qЬЙ Ьблнзку ДмССЙк бл млЙЗ нз нк~ЕЙ С~ìäíëK qЬЙ С~мдн гЙлл~ЦЙл ~кЙ

лнзкЙЗ бе нЬЙ Ьблнзку ДмССЙк бе нЬЙ зкЗЙк зС нЬЙбк çÅÅìêêÉåÅÉK
qЬЙ Ьблнзку ДмССЙк Ь~л Q гЙгзку дзЕ~нбзел пЬбЕЬ Е~е ДЙ ~ЗЗкЙллЙЗ

об~ ÅçÇÉëK

Structure of the history buffer

Code

C0168

Entry

Note

C161 Memory locations 1 Active fault

If the fault is no longer active or has been

acknowledged:

C162 Memory location 2 Last fault

acknowledged:
D

The contents of the memory locations 1-3 will be

saved in a ”higher” location

C163 Memory location 3 Last but one fault

saved in a ”higher” location.

D

The contents of the memory location 4 will be

eliminated from the history buffer and cannot be

C164 Memory location 4 Last but two fault

y

eliminated from the history buffer and cannot be

read any longer.

D

Memory location 1 will be deleted (= no active fault).