3 fault indications, Troubleshooting and fault elimination – Lenze 8200 series User Manual

Page 61

Advertising
background image

Troubleshooting and fault elimination

UOMu_^MVMO

8-3

8.3 Fault indications

Display

Fault

Cause

Remedy

---

No fault

-

-

EEr

External fault (TRIP-Set)

A digital input assigned to the

TRIP-Set function has been

activated

Check external encoder

H05

Internal fault

Contact Lenze

LU

Undervoltage

DC-bus voltage too low

D

Check mains voltage

D

Check supply module

OC1

Short circuit

Short circuit

Find out cause of short circuit; check

cable

Excessive capacitive charging

current of the motor cable

Use motor cable which is shorter or of

lower capacitance

OC2

Earth fault

Grounded motor phase

Check motor; check cable

OC2

Earth fault

Excessive capacitive charging

current of the motor cable

Use motor cable which is shorter or of

lower capacitance

OC3

Overload inverter during

acceleration or short

circuit

Acceleration time too short

(C012)

D

Increase acceleration time

D

Check drive selection

circuit

Defective motor cable

Check wiring

Interturn fault in the motor

Check motor

OC4

Overload controller during

deceleration

Deceleration time too short

(C013)

D

Increase deceleration time

D

Check the selection of the brake

resistor or connect the brake

chopper

OC5

I x t overload

Frequent and too long

acceleration processes with

overcurrent

Check drive dimensioning

Permanent overload with

I

motor

> 1.05 x I

Nx

OC6

Overload motor

Motor is thermally overloaded, for

instance, because of
D

impermissible continuous

current

D

Check drive selection

D

frequent or too long

acceleration processes

D

Check the setting under C120