Commissioning – Lenze 8200 series User Manual

Page 46

Advertising
background image

Commissioning

5-14

UOMu_^MVMO

3.Set the Vmin boost

(C016).

D

Load-independentboost of the motor voltage for field frequencies below the

U/f-rated frequency. You can thus optimize the torque performance of the inverter

drive.

D

It is absolutely necessary to adapt the asynchronous motor used, since otherwise,

the motor can be destroyed by overtemperatue:

Adjustment
Please note the thermal characteristic of the connected motor under small field

frequencies:
D

Usually, standard asynchronous motors with insulation class B can be operated for a

short time with rated current and frequencies between 0Hz ≤ f

d

≤25Hz.

D

Please ask the motor manufacturer for the exact setting values for the motor

current.

A Operate the motor in idle running with a slip frequency of f

d

≈:

- P

mot

≤7.5 kW: f

d

≈5 Hz

- P

mot

>7.5 kW: f

d

≈2 Hz

B Increase V

min

until you reach the following motor current:

-

Motor in short-term operation at 0Hz ≤f

d

≤ 25Hz:

with self-ventilated motors:

I

motor

≤ I

N motor

with forced-ventilated motors:

I

motor

≤ I

N motor

-

Motor in permanent operation at 0Hz ≤f

d

≤ 25Hz:

with self-ventilated motors

I

motor

≤ 0.8 ¡I

N motor

with forced-ventilated motors:

I

motor

≤ I

N motor

4.Set slip compensation

(C021)

Rough setting by means of the motor data:

Set s p co pe sat o

(C021).

л =

е

клуе

− е

к

е

клуе

⋅ NMMB

е

клуе

=

С

Зк

⋅ SM

é

s

Slip constant (C021)

n

rsyn

synchronous motor speed [min

-1

]

n

r

rated speed to motor nameplate [min

-1

]

f

dr

rated frequency to motor nameplate [Hz]

p

Number of pole pairs

Precise setting:
Change C021 under constant load until the speed is near the synchronous speed.
If C021 is set to too high values, the drive may become instable (overcompensation).