3 setting of the current limit (imax), Commissioning, 3 setting of the current limit (i – Lenze 8200 series User Manual

Page 39

Advertising
background image

Commissioning

UOMu_^MVMO

5-7

5.3.3

Setting of the current limit (I

max

)

Code

Name

Possible settings

IMPORTANT

Lenze Selection

Info

C022 I

max

limit

motor mode

150

30

{1 %}

150

C023 I

max

limit

generator mode

80

30

{1 %}

110

Function

The controllers are equipped with a current-limit control which determines the

dynamic response under load. The measured load is compared with the limit values

set under C022 for motor load and under C023 for generator load. If the current-limit

values are exceeded, the controller will change its dynamic response.

Adjustment

The acceleration and decleration time should be set short enough so that the drive can

follow the speed profile without reaching I

max

of the controller.

Drive characteristic

when reaching the limit

value

D

During acceleration:
- Expansion of the acceleration ramp.

D

During deceleration:
- Expansion of the deceleration ramp.

D

When the load increases at constant speed:
- When the motor-current limit value is reached:

Reduction of the field frequency to 10Hz.

- When the generator-current limit value is reached:

Increase the field frequency to the maximum frequency (C011).

- Stop the field-frequency change if the load falls below the limit value.