Commissioning
UOMu_^MVMO
5-5
Important
D
With the setting of f
dmin
> f
dmax
the field frequency is limited to f
dmax
.
D
When selecting the setpoint by means of JOG values, f
dmax
acts as limitation.
D
f
dmax
is an internal standardization variable:
- Use the LECOM interface only for important modifications, when the controller is
inhibited.
D
Observe the maximum motor speed!
D
f
dmin
is only effective under the following conditions:
- With analog setpoint selection.
- With the motor potentiometer function ”DOWN”.
Special features
D
With field frequencies f
d
> 240Hz:
- The overcurrent switch-off can be activated.
fd
C011
(fdmax)
C010
(fdmin)
0 %
100 %