Commissioning

UOMu_^MVMO

5-5

Important

D

With the setting of f

dmin

> f

dmax

the field frequency is limited to f

dmax

.

D

When selecting the setpoint by means of JOG values, f

dmax

acts as limitation.

D

f

dmax

is an internal standardization variable:

- Use the LECOM interface only for important modifications, when the controller is

inhibited.

D

Observe the maximum motor speed!

D

f

dmin

is only effective under the following conditions:

- With analog setpoint selection.
- With the motor potentiometer function ”DOWN”.

Special features

D

With field frequencies f

d

> 240Hz:

- The overcurrent switch-off can be activated.

fd

C011
(fdmax)

C010
(fdmin)

0 %

100 %

hPRKMMSO