Chapter 4 PAS
Application Software

Configuring Communication Protocols

Series PM174 Powermeters

101

Parameter Options Default Description
Binary Counter
Change Event
Object

32-bit -Time
32-bit +Time
16-bit -Time
16-bit +Time

32-bit +Time The default BC change event object

variation for requests with qualifier code
06 when no specific variation is
requested

Frozen Binary

Counter Object

32-bit +Flag
32-bit –Flag
32-bit +Time
16-bit +Flag
16-bit –Flag
16-bit +Time

32-bit -Flag

The default frozen BC object variation

for requests with qualifier code 06 when
no specific variation is requested

DNP General Options
16-bit AI
Scaling

Disabled
Enabled

Enabled

Allows scaling 16-bit analog input
objects (see description below)

16-bit BC

Scaling

x1, x10, x100,
x1000

x1

Allows scaling 16-bit binary counter

objects (see description below)

Re-mapping
Event Points

Disabled
Enabled

Disabled

Allows re-mapping event points starting
with point 0.

SBO Timeout

1

2-30 sec

10

Defines the Select Before Operate

(SBO) timeout when using the Control-
Relay-Output-Block object

Time Sync
Period

2

0-86400 sec

86400

Defines the time interval between
periodic time synchronization requests

Multi Fragment

Interval

50-500 ms

50

Defines the time interval between

fragments of the response message
when it is fragmented

1

The Select Before Operate command causes the device to start a
timer. The following Operate command must be sent before the
specified timeout value expires.

2

The device requests time synchronization by bit 4 in the first octet of

the internal indication word being set to 1 when the time interval
specified by the Time Sync Period elapses. The master should
synchronize the time in the device by sending the Time and Date
object to clear this bit. The device does not send time synchronization
requests if the Time Sync Period is set to 0.

3

The total number of AI, BI and BC change event points may not
exceed 64. When you change the number of the change event
points in the device, all event setpoints are set to defaults
(see Configuring DNP Event Classes below).

Scaling 16-bit AI objects

Scaling 16-bit AI objects allows accommodating native 32-bit
analog input readings to 16-bit object format; otherwise it may
cause an over-range error if the full-range value exceeds a 16-
bit point limit.

Scaling is enabled by default. It is not applied to points that are

read using 32-bit AI objects.

Refer to the PM174 DNP3 Reference Guide for information on
the data point scales and on a reverse conversion that should
be applied to the received scaled values.

Scaling 16-bit Binary Counters

Scaling 16-bit Binary Counters allows changing a counter unit
in powers of 10 to accommodate a 32-bit counter value to 16-
bit BC object format.

If the scaling unit is greater than 1, the counter value is
reported being divided by the selected scaling unit from 10 to
1000. To get the actual value, multiply the counter reading by
the scaling unit.