Chapter 4 PAS Application

Configuring Communications in your

66

Series PM174 Powermeters

data. PAS automatically truncates your range if you

specify more data than the exchange can accommodate.
To indicate the end of the address range list, put a zero
start point ID in the range following the last range you
specified.

6. Click on Send to download your new setup to the meter.

The device will reject your setup if you specified an
inexistent start point ID for one of the address ranges. If
you specified more points in a range than the device can
provide, it truncates the range to the maximum number of

points available.

You can also temporarily put a configured exchange into the
pending (disabled) state, and then resume (enable) it
whenever needed.

NOTE

When you change the consumer IP address through the
Ethernet, the device port restarts and communications will be
temporarily lost, so you may need to wait until PAS restores a
connection with your device.