Configuring the waveform recorder – SATEC PM174 Manual User Manual

Page 94

Advertising
background image

Chapter 4 PAS Application Configuring

Recorders

94

Series PM174 Powermeters

3. Select the TOU Daily profile file type.
4. Select the number of season tariffs in your TOU schedule.

Add one additional parameter if you selected to record the

Summary (TOU total) registers as well.

5. Select the maximum number of records you want to be

recorded in the file assuming that a new record will be
added once a day.

6. Click OK and send your setup to the meter or save to the

database.

Configuring the Waveform Recorder

Waveform log files are organized as multi-section files that

store data for each recording channel in a separate section. A
waveform log file stores up to 6 channels simultaneously:
three voltage and three current channels.

A single channel waveform record contains 512 points of the

sampled input signal. If a waveform log is configured to record
more samples per event than a single record can hold, the
waveform recorder stores as many records per event as
required to record the entire event. All waveform records
related to the event are merged in a series and have the same

series number, so they can be plotted together.

The PM174 supports two waveform files that record
waveforms at three programmable sampling rates: 32, 64 or
128 samples per cycle.

To configure a waveform log file:

1. Double click on a waveform log partition with the left mouse

button.

2. Select a file type for your file.

Advertising