Chapter 4 PAS
Application Software

Configuring Recorders

Series PM174 Powermeters

91

Configuring the Event Recorder

To configure the Event log file:

1. Double click on the Event Log file partition with the left

mouse button.

2. Select a file type for your file.
3. Select the maximum number of records you want to be

recorded in the file.

4. Click OK, then send your new setup to the meter or save

to the device database.

By default, the Event recorder stores all events related to
configuration changes, resets, and device diagnostics. In

addition, it records events related to setpoint operations. Each
setpoint should be individually enabled for recording to the
Event log.

To log setpoint operations, add the “Event log” action to the
setpoint actions list. When a setpoint event happens, the

Event recorder logs all setpoint conditions that caused the
event and all setpoint actions performed in response to the
event. Logging actions themselves will not be recorded to the
Event log.

Configuring the Data Recorder

The Data recorder is programmable to record up to 16 data
parameters per record in each of 16 data log files. The list of

parameters to be recorded to a data log is configured
individually for each file.

Conventional Data Log Files

To create a new data log file or re-configure an existing file:

1. Double click on the file partition with

the left mouse button.