Timers setup, Display setup – SATEC PM174 Manual User Manual

Page 54

Advertising
background image

Chapter 3 Display

Menu Operations

54

Series PM174 Powermeters

Timers Setup

The PM174 is provided with four interval timers. When
enabled, a timer generates periodic events in predefined
intervals that can trigger setpoints to produce periodic actions
like periodic data trending. To enter the menu, select the “t-r”

entry from the main menu and press the ENTER button.

Use the UP and DOWN arrow buttons to scroll to the desired
timer.

To change the time period for the timer:

1. Press the SELECT button to activate the lower window.
2. Use the UP and DOWN arrow buttons to enter the desired

interval value in seconds. Intervals from 1 to 9999

seconds are allowed. Resetting the interval to 0 disables
the timer.

3. Press ENTER to confirm your changes and to save the

new settings, or press ESC to discard changes.

4. You are returned to the middle window to select another

timer or exit the menu.

To exit the menu, press ESC.

Display Setup

This menu allows you to configure options for the meter
display, and view display and device firmware versions. To
enter the menu, select the “diSP” entry from the main menu
and press the ENTER button.

To select a setup option:

1. Press the SELECT button to activate the middle window.
2. Use the UP and DOWN arrow buttons to scroll to the

desired option.

To change the option:

1. Press the SELECT button to activate the lower window.
2. Use the UP and DOWN arrow buttons to select the

desired option.

3. Press ENTER to confirm your changes and to save the

new setting, or press ESC to discard changes.

To exit the menu, press ESC.

The following table lists available options.

Label Parameter

Options Default Description

UPdt

Display update rate 0.1-10.0 sec 1 sec

Defines the interval between
display updates

ScrL

Auto scroll interval

None,
2-15 sec

None

Defines the scroll interval for
the main data display or
disables auto scroll

rEtn

Auto return to the
main screen

diS =
disabled,

En =
Enabled

Enabled

Enables automatic return to
the main display if no buttons

are pressed for 5 minutes

bAr Reference

load

current for LED bar
graph

0-20,000A
(0 = CT
primary
current)

0

Defines the nominal load
(100%) level for the bar
graph display

Uolt Primary/Secondary

volts units

Pri, SEc

Primary

Selects primary or secondary
units for volts display

Ph.P Phase

powers

display mode

diS, En

Disabled

Disables or enables phase
powers in the main display

t-r

0

t-r.1

diSP

1.0

UPdt