Power calculation modes – SATEC PM174 Manual User Manual

Page 69

Advertising
background image

Chapter 4 PAS
Application Software

General Meter Setup

Series PM174 Powermeters

69

Parameter Options

Default Description

Energy Roll Value 1000.0 kWh

10000.0 kWh
100000.0 kWh
1000000.0 kWh
10000000.0 kWh
100000000.0 kWh

100000000.0 The value at which energy

counters roll over to zero

Phase Energy
Calculation

Disabled, Enabled

Disabled

Enables phase energy calculations

Analog Expander
Option

1

Disabled
0-20 mA
4-20 mA
0-1 mA
±1 mA

Disabled

Enables outputs for the AX-8
analog expanders through port

COM2. See “Programming the
Analog Expander”

Backup Battery

OFF = switched OFF
On = switched ON

OFF

Allows to conserve a battery while

the meter is out of operation

Energy Test Mode OFF = disabled

Wh pulses
varh pulses

Disabled

Setting this option puts the meter
into the energy test mode

Volts Scale, V

10-828 V

144 V

The maximum voltage scale

allowed, in secondary volts. See

Data Scales

in Appendix E.

Amps Scale, A

2

× nominal CT

secondary current
(2A, 10A)

2A/10 A

The maximum current scale
allowed, in secondary amps. Not
changeable. See

Data Scales

in

Appendix E.

1

Do not enable the analog expander output if you do not have the

analog expander connected to the meter, otherwise it will disturb the
computer communications.

Power Calculation Modes

The power calculation mode option allows you to change the

method for calculating reactive and apparent powers in
presence of high harmonics. The options work as follows: