Simple reset of accumulated data, Common measurements display – SATEC PM174 Manual User Manual

Page 36

Advertising
background image

Chapter 3 Display

Data Display

36

Series PM174 Powermeters

Pressing both the UP and DOWN arrow buttons together

returns to the first page within the current display.

The SELECT button operates once it’s released. The button
has two functions:

When pressed briefly, it switches to programming

mode.

When pressed together with the ENTER button for

more than 5 seconds, it resets Min/Max records,
maximum demands, or energies depending on the
currently displayed page. If the meter is password

protected, and a simple reset of data from the display
is not allowed, the action has no effect.

The ENERGY button switches to the Energy display. If TOU
registers are configured in the meter, you can repeatedly press
this button to scroll through all available TOU registers. When

briefly pressed once again, it switches back to the common
measurements display

Simple Reset of Accumulated Data

When the meter is not password protected, or the simple reset
of data is allowed from the display regardless of the security
setting (see “Display Setup”), the meter allows the simple
“two-button’ reset of the Min/Max registers, maximum
demands, energies, and counters from the data display mode

without entering the reset menu:

1. Select a display page where the data

you want to reset is displayed:
Min/Max log - select a Min/Max page from the Min/Max

Display.
Ampere and volt maximum demands - select the ampere

or volt maximum demand page from the Min/Max Display.
Power maximum demands - select the power maximum

demand page from the Min/Max Display.
Total and phase energies - select a total energy, or phase
energy page from the Energy Display.
Counters – select a counter page from the Status Display

2.

While holding the SELECT button,

press and hold the ENTER button for

about 5 seconds. The displayed data is
reset to zero.

Common Measurements Display

Scroll through pages with the UP and DOWN arrow buttons.

Common Measurements (Main Display)

1


L

V12
V23

V31

Line-to-line volts

2



P

V1
V2
V3

Line-to-neutral volts (in
configurations with a
neutral wire: 4LN3,
3LN3, 3BLN3, 4LL3,

3LL3, and 3BLL3)

3 I1

I2
I3

Amps

4

kVA/MVA
PF
kW/MW

Total VA
Total PF
Total W