Using Control Setpoints

The PM174 has an embedded logical controller that runs
different actions in response to user-defined internal and
external events. Unlike a PLC, the meter uses a simplified
programming technique based on setpoints that allows the

user to define a logical expression based on measured analog
and digital values that produce a required action.

The meter provides 16 control setpoints with programmable
operate and release delays. Each setpoint evaluates a logical

expression with up to four arguments using OR/AND logic.
Whenever an expression is evaluated as “true”, the setpoint
performs up to four concurrent actions that can send a
command to the output relays, increment or decrement a

counter, or trigger a recorder.

The logical controller provides very fast response to events.
The scan time for all setpoints is 1/2 cycle time (8.8 ms at
60Hz and 10 ms at 50 Hz).

To program the setpoints, select General Setup from the Meter

Setup menu, and then click on the Control/Alarm Setpoints
tab.

The available setpoint options are described in the following
table.

Option Range Description

Triggers

OR/AND

OR, AND

The logical operator for the trigger

Trigger

parameter

See Appendix C The trigger parameter that is used as an argument in

the logical expression

Operate limit

The threshold (in primary units) at which the
conditional expression would be evaluated to true.
Not applicable for digital triggers.