Configuring device memory, Configuring recorders – SATEC PM174 Manual User Manual

Page 89

Advertising
background image

Chapter 4 PAS
Application Software

Configuring Recorders

Series PM174 Powermeters

89

Configuring Recorders

The PM174 is provided with a 1-Megabyte onboard non-

volatile memory for data, event and waveform recording.

Before using recorders, the device memory should be
partitioned between log files. The device memory is fully
configurable. You can define how much memory to allocate for

each log file. If you want to change the factory settings, follow
the guidelines in the section below.

Configuring Device Memory

The device memory can be partitioned for a total of 20 log
files:

Event log

16 Data logs

2 Waveform logs

IEEE 1159 Power Quality log

To view the present device memory settings, select
Memory/Log from the Meter Setup menu, and then click on the
Log Memory tab.

The following table lists available file options.

Option Range

Description

Type

Wrap-around

Non-wrap
TOU Daily
Profile

Defines the file behavior when it is filled up.
Wrap-around: recording continues over the oldest records.
Non-wrap: recording is stopped until the file is cleared.
TOU Daily Profile: TOU daily profile data log (only for Data log #16).

Size

The memory size allocated to the file. Set automatically depending on
the size of the records and the number of records in the file.

Sections/Channels

0-14

The numbers of sections in a multi-section TOU profile data log file, or

the number of recording channels in a waveform log file

Num. of Records

0-65535

Allocates the file memory for predefined number of records

Advertising