Downloading Setup to the Meter

You can update each setup in your meter one at a time or
download all setups together from the site database.

To update a particular setup in your device, check the On-line
button on the PAS toolbar, select a meter site from the list box

on the toolbar, and then select the desired setup group from
the Meter Setup menu. Click on the tab of the setup you want
to download to the meter, and then click Send.

To download all setups to your device at once, check the On-

line button on the PAS toolbar, select the device site from the
list box on the toolbar, and then select Download Setups from
the Meter Setup menu.

Uploading Setup from the Meter

To upload the setup from the device to the site database,
check the On-line button on the PAS toolbar, select the device
site from the list box on the toolbar, and then select Upload
Setups from the Meter Setup menu.

Authorization

If communications with your device is secured, you are
prompted for the password when you send new setup data to
the meter.

Enter the password and click OK. If your authorization was
successful, you are not prompted for the password again until
you close the dialog window.

Configuring Communications in your Meter

This section describes how to configure communication ports
in your meter through PAS.

Setting Up Communication Ports

To enter the setup dialog, select the device site from the list
box on the PAS toolbar, select Communications Setup from
the Meter Setup menu, and then click on the Serial Ports
Setup tab. In the Port box, select the desired device port.