Chapter 4 PAS
Application Software

General Meter Setup

Series PM174 Powermeters

79

expander with address 0, while channels 9 through 16 are

associated with the analog expander with address 1.

The available analog expander outputs options are described
in the following table.

Option Range

Description

Output
parameter

See Appendix B

Selects the measured parameter to be transmitted
through the analog output channel.

Zero scale

Defines the low engineering scale (in primary units)
for the analog output corresponding to a lowest
(zero) output current (0 or 4 mA)

Full scale

Defines the high engineering scale (in primary units)

for the analog output corresponding to a highest
output current (1 or 20 mA)

Before entering the setup dialog, ensure that you selected the
correct analog current option for your expander on the
Instrument Setup tab in the Tools/Configuration dialog. For
scaling output parameters, see “Programming Analog

Outputs” above.

Ì

Analog expander outputs are not operational until you globally

enable the analog expander option in your meter through the Device
Options menu.

Using Counters

The meter provides four six-digit counters that count different
events.

To configure the device counters, select General Setup from
the Meter Setup menu, then click on the Pulse/Event Counters

tab.

Each counter is independently linked to any digital input and
count input pulses with a programmable scale factor. Each