Pq recorder setup – SATEC PM174 Manual User Manual

Page 97

Advertising
background image

Chapter 4 PAS
Application Software

Configuring Recorders

Series PM174 Powermeters

97

Event
ID

IEEE 1159 category

Trigger parameter Reference

value

Typical
thresholds, %

Event
duration

PQE212 Instantaneous swell

½ cycle RMS voltage Un RMS

110-120%

< 30 cycles

PQE221 Momentary interruption ½ cycle RMS voltage Un RMS

0-10%

< 3 sec

PQE222 Momentary sag

½ cycle RMS voltage Un RMS

80-90%

< 3 sec

PQE223 Momentary swell

½ cycle RMS voltage Un RMS

110-120%

< 3 sec

PQE231 Temporary interruption ½ cycle RMS voltage Un RMS

0-10%

< 1 min

PQE232 Temporary sag

½ cycle RMS voltage Un RMS

80-90%

< 1 min

PQE233 Temporary swell

½ cycle RMS voltage Un RMS

110-120%

< 1 min

PQE31

Sustained interruption

½ cycle RMS voltage Un RMS

0-10%

> 1 min

PQE32

Undervoltage

½ cycle RMS voltage Un RMS

80-90%

> 1 min

PQE33

Overvoltage

½ cycle RMS voltage Un RMS

110-120%

> 1 min

PQE4

Voltage unbalance

3-sec negative
sequence unbalance

No 1-5% Steady

state

PQE52

Harmonics THD

3-sec harmonic THD

No

5-20%

Steady state

PQE53 Interharmonics

THD 3-sec

interharmonic

THD

No 2-8% Steady

state

PQE6 Voltage

fluctuations

(flicker)

10-min Pst

No

1-5

Steady state

PQE7 Frequency

variations 3-sec

frequency

Nominal
frequency

1-6% Steady

state

Un – nominal device voltage

PQ Recorder Setup

The PQ recorder setup allows you to adjust thresholds and
hysteresis for PQ triggers, to define the waveform log options

for PQ events, and to enable or disable the PQ recorder in
your device.

To configure the PQ recorder:

1. Select Memory/Log from the Meter

Setup menu, and then click on the PQ
Recorder tab.

2. Adjust thresholds and hysteresis for

PQ triggers if required.

3. Select the waveform logging options

for PQ events.