Chapter 4 PAS
Application Software

General Meter Setup

Series PM174 Powermeters

71

Parameter Options

Default

Description

DST start month
DST start week
DST start weekday

Month-week-
weekday
Week = 1

st

, 2

nd

, 3

rd

,

4

th

or Last (last week

of the month)

First
Sunday in
April

The date when Daylight Savings Time
begins. The DST switch point is
specified by the month, week of the
month and weekday. By default, DST
starts at 2:00 AM on the first Sunday
in April of each year.

DST end month
DST end week
DST end weekday

Month-week-

weekday
Week = 1

st

, 2

nd

, 3

rd

,

4

th

or Last (last week

of the month)

Last

Sunday in
October

The date when Daylight Savings Time

ends. The DST switch point is
specified by the month, week of the
month and weekday. By default, DST
ends at 2:00 AM on the last Sunday
in October of each year.

Time
synchronization
input

None
DI1
DI2

None

The external port receiving the time
synchronization pulses

Daylight Savings Time

When the daylight savings time is enabled, the meter
automatically adjusts the device clock at 02.00 AM when
daylight savings time begins/ends. The default daylight
savings time change points are preset for the U.S.A.

If the daylight savings time option is disabled, you need to

manually adjust the device clock for daylight savings time.

Time Synchronization Pulses

External time synchronization pulses can be delivered through
one of the digital inputs. If a digital input is selected as the time

synchronization source, the edge of an external pulse adjusts
the device clock at the nearest whole minute. The time
accuracy could be affected by the debounce time of the digital
input, and by the operation delay of the external relay.

Using Digital Inputs

The meter is provided with two digital inputs that can trigger
the alarm/control setpoints to give an alarm on input status
change, or can be linked to the energy/TOU registers to count

pulses from external watt meters, or gas and water meters.

To configure them in your device, select the device site from
the list box on the PAS toolbar, select General Setup from the
Meter Setup menu, and then click on the Digital Inputs tab.