Appendix E Data Scales

148

Series PM174 Powermeters

Appendix E Data Scales

The maximum values for volts, amps and power in the PM174
setup and in communications are limited by the voltage and
current scale settings. See

Device Options

in Chapter 4 on

how to change the voltage scale in your meter.

The following table defines the meter data scales.

Scale Conditions

Range

Maximum voltage
(V max)

All configurations

Voltage scale

× PT Ratio, V

1

Maximum current
(I max)

All configurations

Current scale

× CT Ratio, A

2, 3

Wiring 4LN3, 3LN3, 3BLN3

V max

× I max × 3, W

Maximum Power
(P max)

4

Wiring 4LL3, 3LL3, 3BLL3,

3OP2, 3OP3, 3DIR2

V max

× I max × 2, W

Maximum
frequency

50 or 60 Hz

100 Hz

1

The default voltage scale is 144V. The recommended

voltage scale is 120V+20% = 144V for using with external
PT’s, and 690V+20% = 828V for a direct connection to
power line.

2

CT Ratio = CT primary current/CT secondary current

3

The default current scale is 2

× CT secondary (2.0A with 1A

secondaries and 10.0A with 5A secondaries)

.

4

Maximum power is rounded to whole kilowatts. With PT=1.0,

it is limited to 9,999,000 W.