Com1 settings, Com2 settings, Chapter 3 display operations menu operations – SATEC PM174 Manual User Manual

Page 47: Series pm174 powermeters

Advertising
background image

Chapter 3 Display
Operations

Menu Operations

Series PM174 Powermeters

47

2. Use the UP and DOWN arrow buttons to scroll to the

desired option.

To change the option:

1. Press the SELECT button to activate the lower window.
2. Use the UP and DOWN arrow buttons to select the

desired option.

3. Press ENTER to confirm your changes and to store your

new setting, or press ESC to discard changes.

To exit the menu, press ESC.

The following tables list available port options.

COM1 Settings

Label Parameter Options

Default Description

Prot Communications

protocol

rtu = Modbus RTU
ASCII=Modbus ASCII

dnP3 = DNP3

1

PrFb = Profibus DP

Modbus

RTU

The communications

protocol supported by
the port

rS

Port interface

1

232 = RS-232
485 = RS-485
422 = RS-422
dial = Dial-up Modem
Eth.= Ethernet
PrFb = Profibus DP

Depends
on the
order

For non-serial interfaces
- not changeable;
automatically detected
by the meter

Addr Device

address

Modbus: 1-247
DNP3: 0–65532
Profibus DP: 0-126

1

Device network address

bAud

Baud rate

300-115200 bps

19200 bps The port baud rate

dAtA

Data format and
parity

7E, 8N, 8E

8N

7E data format should
not be used with the
Modbus RTU and DNP3
protocols

H.Sh

Handshaking

(flow control)

nonE=no flow control

SOFt=software
(XON/XOFF)
HArd=hardware (CTS)

None

rtS

RTS mode

nonE = not used

Forc = RTS is
permanently asserted
CtrL = RTS is asserted
during the
transmission

None

1

Selecting the DNP3 protocol on the Ethernet port launches the

DNP3/TCP server along with the Modbus/TCP server allowing
simultaneous connections on both TCP ports. Selecting the Modbus
protocol for the port disables the DNP3/TCP server.

The meter automatically detects a replaceable communication module
and does not allow you to change the interface, baud rate or data
format for the Dial-up modem, and for the Ethernet or Profibus port.

COM2 Settings

Label Parameter Options

Default Description

Prot Communications

protocol

rtu = Modbus RTU
ASCII = Modbus
ASCII
dnP3 = DNP3

Modbus
RTU

The communications
protocol supported by
the port

rS Port

interface

485 = RS-485
422 = RS-422

RS-485

Addr Device

address

Modbus: 1-247
DNP3: 0–65532

1

Device network address