Pin assignments, Preset push button, Network address switches – Rockwell Automation 842E EtherNet/IP Absolute Encoder User Manual User Manual
Page 28: Pin assignments preset push button

20
Rockwell Automation Publication 842E-UM001A-EN-P May 2012
Chapter 4
Installation
Pin assignments
Preset push button
To preset the position of the encoder, remove the screw cover from the back of
the encoder and briefly press the Preset button inside (see figure on page 19 and
“Preset function” on page 40).
Network address switches
You can use the three Network Address switches to set the IP address of the
encoder (see figure on page 19 and “Setting the IP Address” on page 23).
Voltage supply
Pin
Signal
Mating cable
wire color
Function
1
Vs
Brown
Supply voltage 10…30V DC
2
White
Do not use
3
GND
Blue
0V DC (ground)
4
Black
Do not use
Ethernet Link Connections – Link 1 and Link 2
Pin
Signal
Mating Cable
Wire Color
Function
1
TxD+
White orange
Ethernet
2
RxD+
White green
Ethernet
3
TxD–
Orange
Ethernet
4
RxD–
Green
Ethernet
ATTENTION
Pressing the preset push button results in a change of position reading.
This can cause unexpected motion which could result in personal injury or
damage to the product or equipment.
IMPORTANT
Press the preset button briefly, no longer than one second.