In the Configuration tab select:

Message type: CIP generic
Service type: Get attribute single
Service code: (automatically populated)
Source element: Preset_Value_Read (browse to this tag).
Instance: 1
Class: 23*
Attribute: 13*

* hexadecimal values

4.

In the Communication tab, browse to the encoder on the ethernet
network, then click OK.