Product Features 2-3

The values are based on the set value.

The value is applied for a minimum pulse width of 1 ms.

Characteristics

Inputs

Input signals

Start, reset

Input method

No-voltage input via:NPN transistor or switching of contact

Start, reset

Minimum input signal width: 1 or 20 ms (selectable)

Power reset

Minimum power-opening time: 0.5 s (Except for A-3, B-1, and
F mode)

Control output

SPDT contact output: 5 A at 250V AC, resistive load
(cosine=1)
Minimum applied load: 10 mA at 5V DC (failure level: P,
reference value)

External Power Supply

No

Key Protect

Yes

Memory backup

EEP-ROM (overwritten 100,000 times min.), which can store
data for 10 years min.

Accuracy of Operating Time and Setting Error

Power-ON start: +-0.01% +-50 ms max.*
* to be rated against set value
Signal start: +- 0.005 +-30 ms max. *
* to be rated against set value
Signal start at transistor output model: +- 0.005% +-3 ms
max.

If the set value is within the sensor waiting time
(250 ms max.)

Electrical Ratings

Insulation resistance

100 M

Ω min. (at 500V DC)

Dielectric strength

2000V AC, 50/60Hz for 1 min. between current-carrying terminals and
non-current-carrying metal parts
(1000V AC for 24V AC/12 to 24V DC type),
1000V AC, 50/60 Hz for 1 min. between non-continuous contacts

Noise immunity

'+-1.5 kV (between power terminals) for 100 to 240V AC, +-480V for 24V AC/12
to 24VDC, and +-600V (between input terminals), square-wave noise by noise
simulator (pulse width: 100 ns/1

μs, 1-ns rise)

Static immunity

±8 kV (malfunction), ±15 kV (destruction)

Vibration resistance

Malfunction

10…55 Hz with 0.35 mm single amplitude each in three directions for 10 min.

Shock resistance

Malfunction

98 m/s

2

(approx. 10 G) each in three directions

Life expectancy

Mechanical

10 million operations min.

Electrical

100,000 operations min. (5 A at 250V AC, resistive load)

EMC

(EMI) EN61812-1
Emission Enclosure: EN55011 Group1 class A
Emission AC mains: EN55011 Group1 class A
(EMS) EN61812-1
Immunity ESD: EN61000-4-2: 4 kV contact discharge (level2)
8 kV air discharge (level3)
Immunity RF-interference: EN61000-4-3: 10 V/m