Functions 3-17

Output mode TON-1: Flicker ON start 2 (Timer does not reset when power comes ON)

0

0

ON time

OFF time

OFF time

ON time

UP

DOWN

Power

Start signal

Gate

Reset

Control output

Timing diag

ram

* Start signal input is disabled during timing.

Timing starts when the start signal goes ON.
The status of the control output is reversed when time is
up (OFF at start).
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.

Note: Normal output operation will not be possible if

the set time is too short.
Set the value to at least 100 ms (contact output
type).

Power

Output

*

Start signal

input

Timing

OFF

Timing

ON

Timing

OFF

(a + b = ON time)

a

b

Basic Operation

0

0

ON time

OFF time

OFF time

ON time

UP

DOWN

Power

Start signal

Gate

Reset

Control output

Timing diag

ram

* Start signal input is disabled during timing.

Timing starts when the start signal goes ON.
The status of the control output is reversed when time is
up (ON at start).
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.

Note: Normal output operation will not be possible if

the set time is too short.
Set the value to at least 100 ms (contact output
type).

Timing

ON

Timing

OFF

Timing

ON

(a + b = OFF time)

a

b

Power

Output

*

Start signal

input

Basic Operation

Advertising