2-2 Product Features

Engineering Data
(Reference Values)

Specifications

0

1

2

3

4

5

1,000

500

100

50

10

Sw

it

ching oper

at

ions (

1

0

4

)

250V DC/30V
cos =1

250V A C

cos =0.4

Load current (A)

30V DC L/R=7 ms

Reference:A maximum current of 0.15 A can be switched
at 125V DC (cos

φ=1) and a maximum current of 0.1 A

can be switched if L/R is 7 ms. In both cases, a life of
100,000 operations can be expected. The minimum
applicable load is 10 mA at 5V DC (failure level: P).

Electrical Ratings
Pilot Duty Rating

NEMA B300

Rated supply voltage

100 to 240V AC, 24V AC/12 to 24V DC (50/60Hz) (permissible
ripple: 20%(p-p) max.)

Operating voltage range

85%…110% of rated supply voltage

Power consumption

100…240V AC
24V AC/12…24V DC

4.3 VA

3.4 VA/1.7 W

Inrush Current

100…240V AC
24V AC/12…24V DC

3 A
5 A


Make 240V AC

30 A
15 A


Break 240V AC

3 A
1.5 A

Hp at 120V AC

1/4 Hp

Hp at 240V AC

1/3 Hp

Mechanical

Mounting method

Flush mounting, surface mounting, DIN mounting

Display

7-segment, negative transmissive LCD;
Present value (red, 12 mm high characters); Set value (green,
6 mm high characters)

Digits

4 digits

Timer

Time ranges

0.000…9.999 s, 0.00…99.99 s, 0.0…999.9 s, 0…9999 s,
0 min. 0 s…99 min. 59 s, 0.0…999.9 min., 0 h 00 min.…99 h
59 min., 0.0 h…999.9 h, 0 h…9999 h

Timer modes

Elapsed time (Up), remaining time (Down), selectable

Output modes

A, A-1, A-2, A-3, B, B-1, D, E, F, Z, S, toff, ton, toff-1, or ton-1

120V AC

120V AC