Rockwell Automation 700-HX Multifunction Digital Timer User Manual

Page 23

Advertising
background image

Publication 700-UM002B-EN-D - June 2010

3-12 Functions

Output Mode A-1: Signal ON-Delay 2 (Timer resets when power comes ON.)

Output mode A-2: Power ON Delay 1 (Timer resets when power comes ON)

Output mode A-3 Power ON Delay 2 (Timer does not reset when power comes ON)

Output mode B: Repeat Cycle 1 (Timer resets when power comes ON.)

Power

Start signal

Gate

Reset

Control output

Set value

Timing
diagram

UP

DOWN

0

0

Set value

Timing starts when the start signal goes ON, and is
reset when the start signal goes OFF.
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
The control output is controlled using a sustained or
one-shot time period.

*Output is instantaneous when setting is 0.

Basic Operation

Power

Start signal
input

Timing

Output

Power

Start signal

Gate

Reset

Control output

Set value

Timing
diagram

UP

DOWN

0

0

Set value

Timing starts when the reset input goes OFF.
The start signal disables the timing function (i.e., same
function as the gate input).
The control output is controlled using a sustained or
one-shot time period.

*Output is instantaneous when setting is 0.

Basic Operation

Power

Timing

Output

.

Power

Start signal

Gate

Reset

Control output

Set value

Timing
diagram

UP

DOWN

0

0

Set value

t

Timing starts when the reset input goes OFF.
The start signal disables the timing function (i.e.,
same function as the gate input).
The control output is controlled using a sustained or
one-shot time period.

*Output is instantaneous when setting is 0.

Basic Operation

Power

Timing

Output

Sustained

.

Power

Start signal

Gate

Reset

Control output

Set value

Timing
diagram

UP

DOWN

0

0

Set value

Sustained
Output

Timing starts when the start signal goes ON.
The status of the control output is reversed when time
is up (OFF at start).
While the start signal is ON, the timer starts when the

power comes ON or when the reset input goes OFF.

* Normal output operation will not be possible if the

set time is too short.
Set the value to at least 100 ms (contact output
type).

** Start signal input is disabled during timing.

Basic Operation

Power

**

Start signal
input

Timing

Output

Timing

Timing

Timing