Publication 700-UM002B-EN-D - June 2010

5-2 Installation

Input Connections

The input of the 700-HX is no-voltage input only.

No-voltage Inputs (NPN Inputs)

No-voltage Input Signal Levels

Two-wire Sensor

PC or sensor

0 V

Input

Signal input

Reset input

Contact input

Open Collector

(Connection to NPN open
collector output sensor)

(Connection to a voltage out
put sensor)

Sensor

Signal input

Reset input

0 V

Input

Signal input

Reset input

0 V

Input

Voltage Output

700-HX

➀ ➂ ➃

700-HX

➀ ➂ ➃

Operate with transistor ON

Operate with transistor ON

Operate with relay ON

No-contact input

Short-circuit level
Transistor ON
Residual voltage: 2 V max.
Impedance when ON: 1 K

Ω max.

(the leakage current is approximately 12 mA when the
impedance is 0

Ω)

Open level
Transistor OFF
Impedance when OFF: 100 K

Ω minimum.

Contact input

Use contact which can adequately switch 5 mA at 10V
Maximum applicable voltage: 30V DC max.

Signal inp

u

t

Reset inp

u

t

0 V

Inp

u

t

700-HX

➀ ➂ ➃