Publication 700-UM002B-EN-D - June 2010

3-16 Functions

Repeat Cycle Operation

Output mode TOFF: Flicker OFF start 1 (Timer resets when power comes ON)

Output mode TON: Flicker ON start 1 (Timer resets when power comes ON)

Output mode TOFF-1: Flicker OFF start 2 (Timer does not reset when power comes ON)

Power

Start signal

Gate

Reset

Control output

OFF time

Timing
diagram

UP

ON time

Sustained
Output

DOWN

0

OFF time

ON time

0

Timing starts when the start signal goes ON.
The status of the control output is reversed when time
is up (OFF at start).
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.

* Normal output operation will not be possible if the

ON/OFF set time is too short.
Set the value to at least 100 ms (contact output
type).

** Start signal input is disabled during timing.

Basic Operation

Power

**

Start signal
input

Timing
ON

Output

Timing
OFF

Timing
ON

Timing
OFF

Power

Start signal

Gate

Reset

Control output

OFF time

Timing
diagram

UP

ON time

Sustained
Output

DOWN

OFF time

ON time

0

0

Timing starts when the start signal goes ON.
The status of the control output is reversed when time
is up (ON at start).
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.

* Normal output operation will not be possible if the

ON/OFF set time is too short.
Set the value to at least 100 ms (contact output
type).

** Start signal input is disabled during timing.

Basic Operation

Power

**

Start signal
input

Timing
OFF

Output

Timing
ON

Timing
OFF

Timing
ON