Enhanced DeviceNet Adapter’s Parameters

M-S Input Parameter Configurations

The M-S Input (24) parameter has the following five configurable
bits.

Figure B.5

Bits and Corresponding I/O

When you enable Cmd/Stat (4) or datalink (5-8) parameter(s) in the
adapter, you must set the corresponding bit in the M-S Input (24)
parameter if you want the input data to come from the scanner or
master device.

The following table lists possible configurations for the M-S Input
(24) parameter and the types of allocation associated with each.

xxx0, 0000

datalink D

datalink C

datalink B

datalink A

Cmd/Ref

0 = Peer or other input
1 = Master-Slave input

ADAPTER

CONFIGURATION

ALLOCATION (Number Of Words)

Data Size Sent From The Controller To The Adapter

M-S Input

M-S Output

Poll Only

COS Only

Cyclic Only

Poll & COS

Poll &

Cyclic

00000

xxxx0

0

NA

NA

NA

NA

00001

xxxx0

2

NA

NA

NA

NA

00010

xxxx0

2

NA

NA

NA

NA

00011

xxxx0

4

NA

NA

NA

NA

00100

xxxx0

2

NA

NA

NA

NA

00101

xxxx0

4

NA

NA

NA

NA

00110

xxxx0

4

NA

NA

NA

NA

00111

xxxx0

6

NA

NA

NA

NA

01000

xxxx0

2

NA

NA

NA

NA

01001

xxxx0

4

NA

NA

NA

NA

01010

xxxx0

4

NA

NA

NA

NA

01011

xxxx0

6

NA

NA

NA

NA

01100

xxxx0

4

NA

NA

NA

NA

01101

xxxx0

6

NA

NA

NA

NA

01110

xxxx0

6

NA

NA

NA

NA

01111

xxxx0

8

NA

NA

NA

NA

10000

xxxx0

2

NA

NA

NA

NA

10001

xxxx0

4

NA

NA

NA

NA

10010

xxxx0

4

NA

NA

NA

NA

10011

xxxx0

6

NA

NA

NA

NA