Devicenet network status led states, Module status led states – Rockwell Automation 1336-GM6 Enhanced DeviceNet Communications Module User Manual

Page 84

Advertising
background image

8-2

Troubleshooting

DeviceNet Network Status LED
States

The LED closest to the DeviceNet connector is the DeviceNet Status
LED, labeled “NET.” It functions as follows:

Module Status LED States

The middle LED, labeled “MOD,” is the Module Status LED. It
indicates the operation of the Enhanced DeviceNet adapter and
functions as follows:

LED Viewed:

If:

State:

Indicates

Action:

Network

Status LED

LED is off

Not powered/Not
online

No power/Duplicate ID
not completed

1. Verify that the network supply is connected and that
power is reaching the adapter through the connector.
2. Make sure one or more nodes are communicating on
the network.
3. Make sure at least one other node on the network is
operational at the same time and data rate as the
adapter.

LED is flashing
green

Online/Not connected

Passed duplicate
ID/No connection
established

No action needed. The LED is flashing to signify that
there are no open communication connections between
the adapter and any other device. Any connection (I/O or
explicit message) made to the adapter over DeviceNet
will cause the LED to stop flashing and remain steady on
for the duration of any open connection.

LED is steady green

Online/Connected

One or more
connections
established

No action needed.

LED is flashing red

Online/Time-out

I/O connection timed
out

1. Bring controller back onto the network.
2. Reduce traffic or errors on the network so that
messages can get through within the necessary time
frame.

LED is steady red

Network failure

Failed Duplicate ID or
Bus-off

1. Ensure that all nodes have unique addresses.
2. If all node addresses are unique, examine network for
correct media installation.

LED Viewed:

If:

State:

Indicates:

Action:

Module

Status LED

LED is off

Not powered

No power

Ensure that the connected SCANport product is
powered and connected to the adapter.

LED is flashing
green

Waiting for I/O data

Normal operation —
No I/O, or PLC in
program

No action needed. Adapter has passed all operational
tests and is waiting to pass I/O data between the
DeviceNet and SCANport interfaces.

LED is solid green

Operational

Normal operation —
I/O operational

No action needed.

LED is flashing red

Configuration
problem

Bad CRC of Adapter
parameters or flash
program

1. Power cycle the adapter to reset it.
2. Enable an adapter reset via the adapter’s
configuration parameter.
3. Re-flash the adapter.

LED is steady red

Hardware failure

Failed internal or
external RAM test

Replace unit.