Common services get_attribute_all response – Rockwell Automation 1336-GM6 Enhanced DeviceNet Communications Module User Manual

Page 122

Advertising
background image

C-14

DeviceNet Objects

Common Services

Get_Attribute_All Response

Not supported.

At the instance level, the order of attributes returned in the
Get_Attributes_All response is as follows:

Service Code

Implemented for:

Service Name

Class

Instance

0x01

No

Yes

Get_Attribute_All

0x0E

Yes

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single

0x4B

No

Yes

Get_Enum_String

0x05

Yes

No

Reset_Request (sets
all parameters to
default values)

0x15

Yes

No

Restore_Request

0x16

Yes

No

Save_Request

Class Attribute ID

Attribute Name and Default Value

1

Parameter Value

2

Link Path Size

3

Link Path

4

Descriptor

5

Data Type

6

Data Size

7

Parameter Name String, default character count = 0

8

Units String, default character count = 0

9

Help String, default character count = 0

10

Minimum Value default = 0

11

Maximum Value default = 0

12

Default Value default = 0

13

Scaling Multiplier Default = 1

14

Scaling Divisor Default = 1

15

Scaling Base Default = 1

16

Scaling Offset Default = 0

17

Multiplier Link Default = 0

18

Divisor Link Default = 0

19

Base Link Default = 0

20

Offset Link Default = 0

Advertising
This manual is related to the following products: