Using DeviceNet Explicit Messaging
In this example, there were four entries in the fault queue. Notice the
following about the data:
Refer to Appendix C, DeviceNet Objects, for more information on
object descriptions.
Location
Value
Meaning
N30:0
0x0201
TXID of 2. Command 1 (Execute)
N30:1
0x0006
Port 0. Size = 6 bytes (N30:3 – 5)
N30:2
0x0E03
Service E (Get Attribute Single) Node 3
N30:3
0x0097
SCANport Pass-Through Fault Object
N30:4
0x0000
Instance 0 (Class Access)
N30:5
0x0001
Attribute 1 (Number of Fault Queues)
N30:70
0x0201
TXID of 2. Status 1 (Success)
N30:71
0x0006
Port 0. Size = 6 bytes (N30:3 – 5)
N30:72
0x8E03
Service 8E (Get Attribute Single Response)
N30:73
0x0004
4 fault queues
Advertising