Rockwell Automation 1336-GM6 Enhanced DeviceNet Communications Module User Manual

Page 60

Advertising
background image

5-6

Configuring a Scanner to Communicate with the Adapter

Mapping the Output I/O

1. In the Scanner Module dialog box, click the Output tab. (To

display this dialog box, right-click the scanner in the
configuration view. See Figure 5.2.)

Figure 5.7

Output Page on the Scanner Module Dialog Box

If you selected the Automap on Add box (Figure 5.3) in the
Scanlist page (Figure 5.4) and did not change any settings,
RSNetWorx has already mapped the I/O. If I/O is not mapped,
click AutoMap to map it. If you need to change the mapping,
click Advanced and change the settings. Click Help for
assistance.

2. In the Memory box, select a location in scanner memory.

In our example, we are using a 1747-SDN and selected Discrete.

3. In the Start Word box, select the word in memory at which the

data should start. In our example, we selected 1.

Scanner

Memory Locations

1747-SDN

Discrete or M-File

1771-SDN

Block Xfer 62 – 57

Advertising
This manual is related to the following products: