Installation

2-9

7. Reapply power to the SCANport product.

8. Reapply power to the DeviceNet network.

Your 1336-GM6 board is now installed. The SCANport LED is
green. The network and module LEDs are blinking green. If your
module’s LEDs are different, refer to Chapter 8, Troubleshooting, for
more information.

You must now edit the adapter’s node address, and you may want to
edit some of its other parameters. Refer to Chapter 4, Configuring the
Enhanced DeviceNet Adapter Using RSNetWorx for DeviceNet
.

Removing the 1336-GM6 Communications Board

To remove the 1336-GM6 communications board, you need to:

Important: To prevent damage to the board, you must wear a
grounding wrist strap when handling the 1336-GM6 communications
board.

Important: If you are removing the communications board from a
1336 PLUS II, refer to the one-page insert included with the kit for
special mounting instructions.

1. Turn off the power supply to the drive and DeviceNet network.

2. Unscrew (using a 1/8" flathead screwdriver) and then unplug the

DeviceNet connector from the communications board.

3. Unscrew and remove the board’s four mounting screws with a #1

Phillips screwdriver.

4. Making sure not to bend the pins as they slide out of the 14-pin

SCANport header, gently pull the communications board away
from the main control board.

5. Unscrew and remove the four stand-offs from the main control

board.

!

ATTENTION: Remove all power from the SCANport
product before removing the 1336-GM6 board. Failure
to disconnect power may result in death or serious injury.
Verify all power is removed before installing the
1336-GM6 board.