Enhanced DeviceNet Adapter’s Parameters

B-3

SCANport devices that support this function have a group of
parameters for datalink configuration. These parameters are Data In
A1 – D2
and Data Out A1 – D2.

If you intend to use command I/O and/or datalinks, you must do the
following:

1. Access the adapter’s parameters using either a serial connection

(refer to Chapter 3, Configuring the 1203-GU6 Enhanced
DeviceNet Module Using a Serial Connection
) or the DeviceNet
network (refer to Chapter 4, Configuring the Enhanced
DeviceNet Adapter Using RSNetWorx for DeviceNet
).

2. Enable the Cmd/Stat Config (4) parameter and/or desired

DataLink (5 – 8) parameters within the Enhanced DeviceNet
adapter.

Figure B.1

Module I/O Configuration

3. Configure or link the Data In A1– D2 and Data Out A1 – D2

parameters in the SCANport product. Refer to the documentation
for your SCANport product.

4. Configure the M-S Input parameter and M-S Output parameter as

desired. Refer to the “M-S Input Parameter Configurations”
section or the “M-S Output Parameter Configurations” sections in
this chapter.

5. Reset the adapter by setting the Reset Adapter (22) parameter to

Enable.

Reference

Logic Command

DL A2 Inp

DL A1 Inp

DL B2 Inp

DL B1 Inp

DL C2 Inp

DL C1 Inp

DL D2 Inp

DL D1 Inp

Feedback

Logic Status

DL A2 Out

DL A1 Out

DL B2 Out

DL B1 Out

DL C2 Out

DL C1 Out

DL D2 Out

DL D1 Out

Module Input

Module Output

Cmd/Stat Config

Datalink A Config

Datalink B Config

Datalink C Config

Datalink D Config

Data to the

SCANport

Device

Data from the

SCANport

Device

Data from

DeviceNet

Data to

DeviceNet