Table 1.1 RTD Specifications

RTD Type

(1)

Temperature Range Using
0.5 mA Excitation

Temperature Range Using
1.0 mA Excitation

Maximum
Scaled
Resolution

Maximum
Scaled
Repeatability

Copper 426

10

Not allowed

-100 to 260°C (-148 to 500°F)

0.1°C (0.1°F)

±0.2°C (±0.4°F)

Nickel 618

(2)

120

-100 to 260°C (-148 to 500°F)

-100 to 260°C (-148 to 500°F)

0.1°C (0.1°F)

±0.1°C (±0.2°F)

Nickel 672

120

-80 to 260°C (-112 to 500°F)

-80 to 260°C (-112 to 500°F)

0.1°C (0.1°F)

±0.1°C (±0.2°F)

Nickel-Iron
518

604

-100 to 200°C (-148 to 392°F)

-100 to +200°C (-148 to 392°F)

0.1°C (0.1°F)

±0.1°C (±0.2°F)

Platinum 385

100

-200 to 850°C (-328 to 1562°F)

-200 to 850°C (-328 to 1562°F)

0.1°C (0.1°F)

±0.2°C (±0.4°F)

200

-200 to 850°C (-328 to 1562°F)

-200 to 850°C (-328 to 1562°F)

0.1°C (0.1°F)

±0.2°C (±0.4°F)

500

-200 to 850°C (-328 to 1562°F)

-200 to 850°C (-328 to 1562°F)

0.1 °C (0.1 °F)

±0.2°C (±0.4°F)

1000

-200 to 850°C (-328 to 1562°F)

Not Allowed

0.1°C (0.1°F)

±0.2°C (±0.4°F)

Platinum 3916

100

-200C to 630°C (-328 to
1166°F)

-200 to 630°C (-328 to 1166°F)

0.1°C (0.1°F)

±0.2°C (±0.4°F)

200

-200 to 630°C (-328 to 1166°F)

-200 to 630°C (-328 to 1166°F)

0.1°C (0.1°F)

±0.2°C (±0.4°F)

500

-200 to 630°C (-328 to 1166°F)

-200 to 630°C (-328 to 1166°F)

0.1°C (0.1°F)

±0.2°C (±0.4°F)

1000

-200 to 630°C (-328 to 1166°F)

Not Allowed

0.1°C (0.1°F)

±0.2°C (±0.4°F)

(1) Digits following the RTD type represent the temperature coefficient of resistance (

α)

, which is defined as the resistance change per ohm per °C. For instance,

platinum 385 refers to a platinum RTD with

α

= 0.00385 ohm/ohm -°C, or simply 0.00385/°C.

(2) Actual value at 0°C is 100

per DIN standard.