Effects of autocalibration on accuracy, Effects of autocalibration on accuracy -33 – Rockwell Automation 1762-IR4 RTD/Resistance Input Module User Manual

Page 67

Advertising
background image

Publication 1762-UM003A-EN-P - February 2003

Module Data, Status, and Channel Configuration 3-33

Effects of Autocalibration
on Accuracy

The module performs autocalibration to correct for drift errors over
temperature. Autocalibration occurs immediately following
configuration of a previously unselected channel, during power cycle
of enable channels and every 5 minutes if so configured. The table
below shows module accuracy with and without calibration.

Table 3.17 Module Accuracy

Input Type

(1)

With Autocalibration

Without Autocalibration

Maximum Error at 25

°

C (77°F) Maximum Error at 60

°

C

(140°F)

Temperature Drift (0

°

C to 60

°

C)

(32°F to 140°F)

100

Platinum 385

±

0.5

°

C (±0.9°F)

±

0.9

°

C (±1.62°F)

±

0.026

°

C/

°

C (±0.026°F/°F)

200

Platinum 385

±

0.5

°

C (±0.9°F)

±

0.9

°

C (±1.62°F)

±

0.026

°

C/

°

C (±0.026°F/°F)

500

Platinum 385

±

0.5

°

C (±0.9°F)

±

0.9

°

C (±1.62°F)

±

0.026

°

C/

°

C (±0.026°F/°F)

1000

Platinum 385

±

0.5

°

C (±0.9°F)

±

0.9

°

C (±1.62°F)

±

0.026

°

C/

°

C (±0.026°F/°F)

100

Platinum 3916

±

0.4

°

C (±0.72°F)

±

0.8

°

C (±1.44°F)

±

0.023

°

C/

°

C (±0.023°F/°F)

200

Platinum 3916

±

0.4

°

C (±0.72°F)

±

0.8

°

C (±1.44°F)

±

0.023

°

C/

°

C (±0.023°F/°F)

500

Platinum 3916

±

0.4

°

C (±0.72°F)

±

0.8

°

C (±1.44°F)

±

0.023

°

C/

°

C (±0.023°F/°F)

1000

Platinum 3916

±

0.4

°

C (±0.72°F)

±

0.8

°

C (±1.44°F)

±

0.023

°

C/

°

C (±0.023°F/°F)

10

Copper 426

±

0.6

°

C (±1.08°F)

±

1.1

°

C (±1.98°F)

±

0.032

°

C/

°

C (±0.032°F/°F)

120

Nickel 618

±

0.2

°

C (±0.36°F)

±

0.4

°

C (±0.72°F)

±

0.012

°

C/

°

C (±0.012°F/°F)

120

Nickel 672

±

0.2

°

C (±0.36°F)

±

0.4

°

C (±0.72°F)

±

0.012

°

C/

°

C (±0.012°F/°F)

604

Nickel-Iron 518

±

0.3

°

C (±0.54°F)

±

0.5

°

C (±0.9°F)

±

0.015

°

C/

°

C (±0.015°F/°F)

150

±

0.15

±

0.25

±

0.007

/

°

C (±0.012

/°F)

500

±

0.5

±

0.8

±

0.023

/

°

C (±0.041

/°F)

1000

±

1.0

±

1.5

±

0.043

/

°

C (±0.077

/°F)

3000

±

1.5

±

2.5

±

0.072

/

°

C (±0.130

/°F)

(1) The accuracy values apply to both current sources.

Advertising