B-4 Configuring the 1762-IR4 Module Using RSLogix 500

The 1762-IR4 module is installed in slot 1. To configure the module,
double-click on the module/slot. The general configuration screen
appears.

Configuration options for channels 0 to 2 are located on a separate tab
from channel 3, as shown below. To enable a channel, click its Enable
box so that a check mark appears in it. For optimum module
performance, disable any channel that is not hard wired to a real
input. Then, choose your Data Format, Input Type, Filter Frequency,
Open Circuit response, and Units for each channel. You can also
choose to disable cyclic lead compensation for each channel. For
more information on cyclic lead compensation, see Selecting Cyclic
Lead Compensation (Bit 4) on page 3-16
.